Product >> Termination>> 3M Cold Shrink QT-III Termination - Three Conductor 3C 電纜 終端接頭 處理頭
QT-III Silicone Rubber - Three Conductor
3M Three Conductor Cable Termination Kits 7600
Series are designed to terminate medium voltage power cables rated up to 35
kV. 7600-3G series kits are designed for three conductor cables with
internal ground wires. 7600-3W series kits are designed for three conductor
cables without internal ground wires. 7600-RJS series kits are designed for
cabinet-mount installations and can be used on cables with, or without,
internal ground wires. Each termination kit has all of the materials
required to make a three conductor termination (except lugs, which must be
ordered separately).
Kit components include: • The 7600-3W series kits also include a silicone rubber breakout boot. |
產品型號 |
耐衝擊電壓 |
電纜絕緣外徑 O.D. Range |
導體尺寸線徑 AWG AND kcmil (mm2) |
||||
5 kV |
8 kV |
15 kV |
25/ 28 kV |
35 kV |
|||
7620-T-95 |
95 kV |
0.32 – 0.59 (8,1 – 15,0) |
8 – 4 |
8 – 6 |
— |
— |
— |
7621-T-95 |
95 kV |
0.44 – 0.89 (11,2 – 22,6) |
2 – 3/0 |
4 – 2/0 |
— |
— |
— |
7622-T-95 |
95 kV |
0.64 – 1.08 (16,3 – 27,4) |
4/0 – 400 |
3/0 – 300 |
— |
— |
— |
7624-T-95 |
95 kV |
0.83 – 1.53 (21,1 – 38,9) |
500 – 750 |
350 – 700 |
— |
— |
— |
7625-T-95 |
95 kV |
1.05 – 1.80 (26,7 – 45,7) |
700 – 1500 |
600 – 1250 |
— |
— |
— |
7622-T-110 |
110 kV |
0.64 – 1.08 (16,3 – 27,4) |
4/0 – 400 |
3/0 – 300 |
2 – 2/0 (35 – 70) |
— |
— |
7623-T-110 |
110 kV |
0.72 – 1.29 (18,3 – 32,8) |
300 – 500 |
250 – 500 |
2/0 – 300 (70 – 150) |
— |
— |
7624-T-110 |
110 kV |
0.83 – 1.53 (21,1 – 38,9) |
500 – 750 |
350 – 700 |
4/0 – 500 (120 – 240) |
— |
— |
7625-T-110 |
110 kV |
1.05 – 1.80 (26,7 – 45,7) |
700 – 1500 |
600 – 1250 |
500 – 1000 (240 – 500) |
— |
— |
7626-T-110 |
110 kV |
1.53 – 2.32 (38,9 – 58,9) |
1750 – 2000 |
1500 – 2000 |
1250 – 2000 (625 – 1000) |
— |
— |
7693-T-150 |
150 kV |
0.72 – 1.29 (18,3 – 32,8) |
300 – 500 |
250 – 500 |
2/0 – 300 (70 – 150) |
2 – 4/0 (35 – 120) |
2 – 2/0 (35 – 70) |
7695-T-150 |
150 kV |
1.05 – 1.80 (26,7 – 45,7) |
700 – 1500 |
600 – 1250 |
500 – 1000 (240 – 500) |
250 – 800 (150 – 400) |
3/0 – 600 (95 – 325) |
7696-T-150 |
150 kV |
1.53 – 2.32 (38,9 – 58,9) |
1750 – 2000 |
1500 – 2000 |
1250 – 2000 (625 – 1000) |
900 – 1750 (500 – 800) |
700 – 1500 (400 – 725) |
Cable Types for Terminating
3/C Copper Tape Shielded Cable |
|
3/C Copper Tape Shielded Cable - Armored |
Termination Type Selection Guide for Three Conductor Cable 7600 Series
Kit Series |
Insulator Configuration |
Installation Environment |
Orientation |
For Cable Type(s) (With or Without Ground Wires) |
7600-S-3G 7600-T-3G 7690-S-INV-3G 7600-S-3-RJS 7600-T-3-RJS 7690-S-INV-3-RJS 7600-S-3W 7600-T-3W 7690-S-INV-3W |
Skirted Tubular Skirted Skirted Tubular Skirted Skirted Tubular Skirted |
Outdoor Indoor Outdoor Indoor-Cabinet Mount (No Breakout Indoor-Cabinet Mount (No Breakout Indoor-Cabinet Mount (No Breakout Outdoor Indoor Outdoor |
Normal Normal Inverted Normal Normal Inverted Normal Normal Inverted |
With ground wires With ground wires With ground wires With or Without ground wires With or Without ground wires With or Without ground wires Without ground wires Without ground wires Without ground wires |
We have 7600-T-3W, 7600-S-3W, 7690-S-INV-3W in Stock.
7600-T-3W Series — Kit Selection Guide
Kit Number |
BIL kV |
Cable Insulation Range in. (mm) |
3.3 kV (mm2) IEC |
3.3 kV (mm2) JIS |
5.0 kV (AWG) AEIC |
6.6 kV (mm2) JIS |
6.6 kV (mm2) IEC |
8.7 kV (AWG) AEIC |
10 kV (mm2) IEC |
UPC (051131-) |
7620-T-95-3W |
95 |
0.33-0.50 (8.40-12.7) |
16-35 |
8-22 |
8-2 |
— |
16-25 |
6-4 |
— |
04731 |
7621-T-95-3W |
95 |
0.50-0.70 (12.7-17.8) |
50-95 |
38-60 |
1-3/0 |
— |
35-70 |
2-2/0 |
10-50 |
04732 |
7623-T-95-3W |
95 |
0.70-0.92 (17.8-23.4) |
120-185 |
100-150 |
4/0-400 |
— |
95-150 |
3/0-350 |
70-150 |
04733 |
7624-T-95-3W |
95 |
0.92-1.18 (23.4-30.0) |
240-300 |
200-250 |
500-750 |
— |
185-300 |
400-600 |
185-300 |
04734 |
7625-T-95-3W |
95 |
1.18-1.52 (30.0-38.6) |
— |
300-325 |
800-1000 |
— |
— |
750-1000 |
— |
04735 |
7621-T-110-3W |
110 |
0.50-0.70 (12.7-17.8) |
50-95 |
38-60 |
1-3/0 |
14-38 |
35-70 |
2-2/0 |
10-50 |
04736 |
7622-T-110-3W |
110 |
0.70-0.92 (17.8-23.4) |
120-185 |
100-150 |
4/0-400 |
60-100 |
95-150 |
3/0-350 |
70-150 |
04737 |
7624-T-110-3W |
110 |
0.92-1.18 (23.4-30.0) |
240-300 |
200-250 |
500-750 |
150-250 |
185-300 |
400-600 |
185-300 |
04738 |
7625-T-110-3W |
110 |
1.18-1.52 (30.0-38.6) |
— |
300-325 |
800-1000 |
300-325 |
— |
750-1000 |
— |
04739 |
7622-T-125-3W |
125 |
0.70-0.92 (17.8-23.4) |
120-185 |
100-150 |
4/0-400 |
60-100 |
95-150 |
3/0-350 |
70-150 |
04740 |
7624-T-125-3W |
125 |
0.92-1.18 (23.4-30.0) |
240-300 |
200-250 |
500-750 |
150-250 |
185-300 |
400-600 |
185-300 |
04741 |
7625-T-125-3W |
125 |
1.18-1.52 (30.0-38.6) |
— |
300-325 |
800-1000 |
300-325 |
— |
750-1000 |
— |
04742 |
7693-T-150-3W |
150 |
0.70-0.92 (17.8-23.4) |
120-185 |
100-150 |
4/0-400 |
60-100 |
950-150 |
3/0-350 |
70-150 |
41743 |
7694-T-150-3W |
150 |
0.92-1.18 (23.4-30.0) |
240-300 |
200-250 |
500-750 |
150-250 |
185-300 |
400-600 |
185-300 |
04744 |
7695-T-150-3W |
150 |
1.18-1.52 (30.0-38.6) |
— |
300-325 |
800-1000 |
300-325 |
— |
750-1000 |
— |
04745 |
Kit Number |
BIL kV |
Cable Insulation Range in. (mm) |
15 kV (mm2) IEC |
15 kV (AWG) AEIC |
20 kV (mm2) IEC |
25/28 kV (AWG) AEIC |
UPC (051131-) |
7620-T-95-3W |
95 |
0.33-0.50 (8.40-12.7) |
— |
— |
— |
— |
04731 |
7621-T-95-3W |
95 |
0.50-0.70 (12.7-17.8) |
16-25 |
— |
— |
— |
04732 |
7623-T-95-3W |
95 |
0.70-0.92 (17.8 23.4) |
35-95 |
— |
— |
— |
04733 |
7624-T-95-3W |
95 |
0.92-1.18 (23.4-30.0) |
120-185 |
— |
— |
— |
04734 |
7625-T-95-3W |
95 |
1.18-1.52 (30.0-38.6) |
200-325 |
— |
— |
— |
04735 |
7621-T-110-3W |
110 |
0.50-0.70 (12.7-17.8) |
6-25 |
2-1 |
— |
— |
04736 |
7622-T-110-3W |
110 |
0.70-0.92 (17.8-23.4) |
35-95 |
1/0-4/0 |
— |
— |
04737 |
7624-T-110-3W |
110 |
0.92-1.18 (23.4-30.0) |
120-185 |
250-450 |
— |
— |
04738 |
7625-T-110-3W |
110 |
1.18-1.52 (30.0-38.6) |
200-325 |
500-750 |
— |
— |
04739 |
7622-T-125-3W |
125 |
0.70-0.92 (17.8-23.4) |
35-95 |
1/0-4/0 |
25-70 |
— |
04740 |
7624-T-125-3W |
125 |
0.92-1.18 (23.4-30.0) |
120-185 |
250-450 |
95-185 |
— |
04741 |
7625-T-125-3W |
125 |
1.18-1.52 (30.0-38.6) |
200-325 |
500-750 |
240-300 |
— |
04742 |
7693-T-150-3W |
150 |
0.70-0.92 (17.8-23.4) |
35-95 |
1/0-4/0 |
25-70 |
2-1/0 |
04743 |
7694-T-150-3W |
150 |
0.92-1.18 (23.4-30.0) |
120-185 |
250-450 |
95-185 |
2/0-250 |
04744 |
7695-T-150-3W |
150 |
1.18-1.52 (30.0-38.6) |
200-325 |
500-750 |
240-300 |
300-500 |
04745 |
7600-S-3W Series — Kit Selection Guide
Kit Number |
BIL kV |
Cable Insulation Range in. (mm) |
3.3 kV (mm2) IEC |
3.3 kV (mm2) JIS |
5.0 kV (AWG) AEIC |
6.6 kV (mm2) JIS |
6.6 kV (mm2) IEC |
8.7 kV (AWG) AEIC |
10 kV (mm2) IEC |
UPC (051131-) |
7620-S-2-3W |
95 |
0.33-0.50 (8.40-12.7) |
16-35 |
8-22 |
8-2 |
— |
16-25 |
6-4 |
— |
04748 |
7621-S-2-3W |
95 |
0.50-0.70 (12.7-17.8) |
50-95 |
38-60 |
1-3/0 |
— |
35-70 |
2-2/0 |
10-50 |
04749 |
7622-S-2-3W |
110 |
0.70-0.92 (17.8-23.4) |
120-185 |
100-150 |
4/0-400 |
60-100 |
95-150 |
3/0-350 |
70-150 |
04750 |
7691-S-4-3W |
150 |
0.50-0.70 (12.7-17.8) |
50-95 |
38-60 |
1-3/0 |
— |
35-70 |
2-2/0 |
10-50 |
04751 |
7692-S-4-3W |
150 |
0.70-0.92 (17.8-23.4) |
120-185 |
100-150 |
4/0-400 |
60-100 |
95-150 |
3/0-350 |
70-150 |
04752 |
7693-S-4-3W |
150 |
0.92-1.18 (23.4-30.0) |
240-300 |
200-250 |
500-750 |
150-250 |
185-300 |
400-600 |
185-300 |
04753 |
7695-S-4-3W |
150 |
1.18-1.52 (30.0-38.6) |
— |
300-325 |
800-1000 |
300-325 |
— |
750-1000 |
— |
04754 |
7684-S-8-3W |
200 |
0.92-1.18 (23.4-30.0) |
240-300 |
200-250 |
500-750 |
150-250 |
185-300 |
400-600 |
185-300 |
04755 |
7685-S-8-3W |
200 |
1.18-1.52 (30.0-38.6) |
— |
300-325 |
800-1000 |
300-325 |
— |
750-1000 |
— |
04756 |
Kit Number |
BIL kV |
Cable Insulation Range in. (mm) |
15 kV (mm2) IEC |
15 kV (AWG) AEIC |
20 kV (mm2) IEC |
25/28 kV (AWG) AEIC |
30 kV (mm2) IEC |
35 kV (AWG) AEIC |
UPC (051131-) |
7620-S-2-3W |
95 |
0.33-0.50 (8.40-12.7) |
— |
— |
— |
— |
— |
— |
04748 |
7621-S-2-3W |
95 |
0.50-0.70 (12.7-17.8) |
16-25 |
— |
— |
— |
— |
— |
04749 |
7622-S-2-3W |
110 |
0.70-0.92 (17.8-23.4) |
35-95 |
1/0-4/0 |
— |
— |
— |
— |
04750 |
7691-S-4-3W |
150 |
0.50-0.70 (12.7-17.8) |
16-25 |
— |
— |
— |
— |
— |
04751 |
7692-S-4-3W |
150 |
0.70-0.92 (17.8-23.4) |
35-95 |
1/0-4/0 |
25-70 |
2-1/0 |
— |
— |
04752 |
7693-S-4-3W |
150 |
0.92-1.18 (23.4-30.0) |
120-185 |
250-450 |
95-185 |
2/0-250 |
— |
— |
04753 |
7695-S-4-3W |
150 |
1.18-1.52 (30.0-38.6) |
200-325 |
500-750 |
240-300 |
300-500 |
— |
— |
04754 |
7684-S-8-3W |
200 |
0.92-1.18 (23.4-30.0) |
120-185 |
250-450 |
95-185 |
2/0-250 |
35-70 |
1/0-3/0 |
04755 |
7685-S-8-3W |
200 |
1.18-1.52 (30.0-38.6) |
200-325 |
500-750 |
240-300 |
300-500 |
95-240 |
4/0-500 |
04756 |
7690-S-INV-3W Series — Kit Selection Guide
Kit Number |
BIL kV |
Cable Insulation Range in. (mm) |
3.3 kV (mm2) IEC |
3.3 kV (mm2) JIS |
5.0 kV (AWG) AEIC |
6.6 kV (mm2) JIS |
6.6 kV (mm2) IEC |
8.7 kV (AWG) AEIC |
10 kV (mm2) IEC |
UPC (051131-) |
7693-S-4-INV-3W |
150 |
0.92-1.18 (23.4-30.0) |
240-300 |
200-250 |
500-750 |
150-250 |
185-300 |
400-600 |
185-300 |
04746 |
7695-S-4-INV-3W |
150 |
1.18-1.52 (30.0-38.6) |
? |
300-325 |
800-1000 |
300-325 |
? |
750-1000 |
? |
04747 |
Kit Number |
BIL kV |
Cable Insulation Range in. (mm) |
15 kV (mm2) IEC |
15 kV (AWG) AEIC |
20 kV (mm2) IEC |
25/28 kV (AWG) AEIC |
UPC (051131-) |
7693-S-4-INV-3W |
150 |
0.92-1.18 (23.4-30.0) |
120-185 |
250-450 |
95-185 |
2/0-250 |
04746 |
7695-S-4-INV-3W |
150 |
1.18-1.52 (30.0-38.6) |
200-325 |
500-750 |
240-300 |
300-500 |
04747 |
8560 Series 3/C Cable Breakout Boots
8560 Series Breakout Boots are designed to protect the phase leg breakout of 3/C medium voltage power cable from exposure to moisture, contamination, corrosion, ozone, ultra-violet radiation, physical contact and other hazards associated with 3/C termination operating environments. 8560 Series Breakout Boots can be used in conjunction with 3M Silicone Rubber Cold Shrink Rejacketing Sleeves for 3/C shielded power cable terminating applications.
Product Number |
Cable Phase Shield Diameter Range [A] |
Cable Outer Jacket Diameter Range [B] |
pcs/box |
boxes/case |
8561 |
0.48 – 0.72" (12,2 – 18,3 mm) |
1.17 – 1.94" (29,7 – 49,3 mm) |
1 |
16 |
8561 |
0.61 – 0.95" (15,5 – 24,2 mm) |
1.46 – 2.67" (37,1 – 67,8 mm) |
1 |
16 |
8563 |
0.82 – 1.18" (20,8 – 30,0 mm) |
1.92 – 3.10" (48,8 – 78,7 mm) |
1 |
16 |
8564 |
1.02 – 1.63" (26,0 – 41,4 mm) |
2.52 – 4.32" (64,0 – 109,8 mm) |
1 |
16 |
8565 |
1.09 – 1.94" (27,7 – 49,3 mm) |
2.60 – 4.70" (66,1 – 119,4 mm) |
1 |
16 |
3M 3/C Phase Rejacketing System
Rejacketing sleeves are designed to protect the phase legs (core) of 3/C shielded power cable from exposure to moisture, corrosion, ozone, ultra-violet radiation, physical contact and other hazards that are associated with termination operating environments. Rejacketing sleeves are designed to be used in conjunction with 3M Cold Shrink Breakout Boots and Silicone Rubber Terminations.
Product Number |
Metallic Shield Diameter Range |
3.3 KV (mm2) IEC |
3.3 KV (mm2) JIS |
5.0 KV (AWG) AEIC |
6.6 KV (mm2) IEC |
6.6 KV (mm2) JIS |
8.0 KV (AWG) AEIC |
RJS – 1 |
0.43 – 0.60" 10,9 – 15,2 mm |
16 – 35 |
8 – 22 |
8 – 2 |
16 – 25 |
8 – 10 |
6 – 4 |
RJS – 2 |
0.60 – 0.80" 15,2 – 20,3 mm |
50 – 95 |
38-60 |
1 – 3/0 |
35 – 70 |
14 – 38 |
2 – 2/0 |
RJS – 3 |
0.80 – 1.02" 20,3 – 26,0 mm |
120 – 185 |
100 – 150 |
4/0 – 400 |
95 – 150 |
60 – 100 |
3/0 – 350 |
RJS – 4 |
1.02 – 1.28" 25,9 – 32,4 mm |
240 – 300 |
200 – 250 |
500 – 750 |
185 – 300 |
150 – 250 |
400 – 600 |
RJS – 5 |
1.28 – 1.62" |
— |
300 – 325 |
800 – 1000 |
— |
300 – 325 |
750 – 1000 |
Product Number |
Metallic Shield Diameter Range |
10 KV (mm2) IEC |
15 KV (AWG) AEIC |
20 KV (mm2) IEC |
25 KV (AWG) AEIC |
30 KV (mm2) IEC |
35 KV (AWG) AEIC |
RJS – 1 |
0.43 – 0.60" 10,9 — 15,2 mm |
— |
— |
— |
— |
— |
— |
RJS – 2 |
0.60 – 0.80" 15,2 – 20,3 mm |
10 – 50 |
2 – 1 |
— |
— |
— |
— |
RJS – 3 |
0.80 – 1.20" 20,3 – 26,0 mm |
70 – 150 |
1/0 – 4/0 |
25 – 70 |
2 – 1/0 |
|
|
RJS – 4 |
1.02 – 1.28" 25,9 – 32,4 mm |
185 – 300 |
250 – 450 |
95 – 185 |
2/0 – 250 |
35 – 70 |
1/0 – 3/0 |
RJS – 5 |
1.28 – 1.62" |
— |
500 – 750 |
240 – 300 |
300 – 500 |
95 – 240 |
4/0 – 500 |
您可能會需要:
Tubular Cable Lug 加長型 (高壓) 單孔銅管端子/加長型 (高壓) 雙孔銅管端子
For other QT-II termination 其他 3M QT-II電纜處理頭
3M Cable Cleaning System 電纜清潔劑